6.15. Valve

../_images/image1256.svg

Fig. 6.15.1 Schematic of a Heat valve.

Fall type

Type label

Description

Active

Heat Valve

Control or block valve with choice out of four predefined Deltares standard head loss characteristics or user specified characteristics; several initial settings can be used for flow or pressure balancing

Yes

6.15.1. Mathematical model

6.15.1.1. Pressure loss coefficients

The discharge characteristic indicates the relation between the flow \(Q\) through the valve and the pressure loss \(\Delta p\) across the valve as a function of the valve position. This relation is expressed in a discharge coefficient \(K_v\) or \(C_v\) and a loss coefficient \(\xi\).

The coefficients are derived from the general equation for a Newtonian flow through a restriction in a pipeline under cavitation free circumstances:

(6.15.1)\[\Delta p = \xi\frac{\rho_{1}v_{1}^{2}}{2}\]

with:

Variable

Description

Units

\(\Delta p\)

Pressure difference over the valve

Pa

\(\xi\)

Loss coefficient of the valve

-

\(\rho_1\)

Density of the fluid (upstream)

kg/m3

\(v_1\)

Velocity of the fluid (upstream)

m/s

In practice the discharge coefficients \(K_v\) is often used:

(6.15.2)\[K_{v}=\frac{Q}{\sqrt{\Delta p}}\]

with:

Variable

Description

Units

\(K_v\)

Discharge coefficient

m3 /h/\(\sqrt{\text{bar}}\)

\(Q\)

Flowrate

m3/h

\(\Delta p\)

Pressure difference over the valve

bar

In words: the discharge coefficient Kv denotes the flow in m3/h which flows through a valve at a pressure difference of 1 bar.

Apart from \(K_v\), \(C_v\) is also defined as a discharge coefficients for American units.

(6.15.3)\[C_{v}=\frac{Q}{\sqrt{\Delta p}}\]

with

Variable

Description

Units

\(C_v\)

Discharge coefficient

USGM/ \(\sqrt{\text{psi}}\)

\(Q\)

Flowrate

USGM

\(\Delta p\)

Pressure difference over the valve

psi

The relation between ξ, Kv and Cv is as follows:

(6.15.4)\[\xi=1.6 \cdot 10^{9} \frac{1}{K_{v}^{2}} \cdot D^{4}\]
(6.15.5)\[K_{v}=0.865 C_{v}\]

A valve is characterised by ξ = f (θ) or Kv = f (θ) or Cv = f (θ).

θ denotes the dimensionless valve opening. θ ranges from 0 to 1 (in SI-units, or 0 = 100 % in percentage annotation)

  • θ = 0, valve is closed.

  • θ = 1, valve is completely open.

The different discharge characteristic are always translated to the following equation:

(6.15.6)\[\Delta H = a\xi Q_{1}|Q_{1}|\]

with:

Variable

Description

Units

\(\Delta H\)

\(H_1 - H_2\) in the positive flow direction

m

\(H_1 / H_2\)

Upstream and downstream head

m

\(a\)

\(1 / \left(2 g A_f^2 \right)\)

s2/m5

\(\xi\)

Loss coefficient

-

\(Q_1\)

Upstream discharge

m3/s

The discharge characteristic may be defined by one of Deltares’ standard characteristics (See Hydraulic specifications) or by a user-defined discharge characteristic. If the valve position does not coincide with a tabulated position, interpolation must be performed to obtain the discharge coefficient for intermediate valve positions. The standard characteristics and the user-defined ξ characteristic are interpolated logarithmically according to the following equation:

(6.15.7)\[\theta (z) = z \theta_1 + \left( 1 - z \right) \theta_2\]
(6.15.8)\[\xi\left( \theta (z) \right) = \xi_1^z \xi_2^{1 - z}\]

The user-defined Kv and Cv characteristics are interpolated such that Kv or Cv values are interpolated linearly:

(6.15.9)\[\frac{1}{\sqrt{\xi\left( \theta (z) \right)}} = \frac{z}{\sqrt{\xi_{1}}} + \frac{1 - z}{\sqrt{\xi_{2}}}\]

with:

Variable

Description

Units

\(\theta_1, \theta_2\)

Tabulated valve opening positions

-

\(z\)

Fraction defining intermediate valve position (\(0 < z < 1\))

-

\(\theta (z)\)

Intermediate valve position loss coefficient

-

\(\xi ( \theta (z))\)

Interpolated loss coefficient

-

If the valve is closed the governing equations is:

(6.15.10)\[Q_{1} = 0\]

To calculate the temperature the following equation is used:

(6.15.11)\[\dot{m}c_{p, 1}T_{1} - \dot{m}c_{p, 2}T_{2} + fr Q_{\text{gen}} = 0\]

with:

Variable

Description

Units

\(\dot{m}\)

Mass flow rate

kg/s

\(c_{p, i}\)

Specific heat at connection point \(i\)

J/kg/K

\(T_{i}\)

Temperature at connection point \(i\)

K

\(fr\)

Fraction generated heat supplied to fluid

-

\(Q_{gen}\)

Heat generated by friction

W

The generated heat is given by:

(6.15.12)\[Q_{gen} = \xi \frac{\dot{m}^3}{2 \rho^2 A^2}\]

Variable

Description

Units

\(A\)

Area of the valve

m2

6.15.1.2. Cavitation

Cavitation depends on the pressure conditions around the valve. Usually these pressure conditions are defined by a pressure relation. Several different definitions are used in industrial standards.

In WANDA the factor \(X_f\) is used, according the German VDMA standard.

(6.15.13)\[X_{f} = \frac{\Delta p}{p_1 - p_v}\]

with:

Variable

Description

Units

\(X_f\)

Pressure ratio

-

\(\Delta p\)

Pressure difference over valve

Pa

\(p_1\)

Absolute pressure upstream of the valve

Pa abs

\(p_v\)

Vapour pressure of the fluid

Pa

The pressure ratio depends of the valve opening: Xf = f (θ)

The pressure ratio Xf is only calculated for positive flow; for negative flow Xf = 0.

If the cavitation characteristic is specified, the program calculates the pressure ratio in the system and warns the user if it exceeds the available value as defined in the characteristic.

Note:

In other standards (ISA, BS, IEC) the pressure ratio \(X_{T}\)is used:

(6.15.14)\[X_{T} = \frac{p_{1} - p_{2}}{p_{1}} = \frac{\Delta p}{p_{1}}\]

In some standards (e.g. ISA) the Thoma number (\(\sigma\)) is used.

(6.15.15)\[\sigma_{} = \frac{p_1 - p_v}{\Delta p}\]

with:

Variable

Description

Units

\(X_f\)

Pressure ratio

\(\Delta p\)

Pressure difference over valve

Pa

\(p_1\)

Absolute pressure upstream of the valve

Pa abs

\(p_v\)

Vapour pressure of the fluid

Pa

The relationship between Xf and σ is:

(6.15.16)\[\sigma_{} = \frac{1}{X_{f}}\]

Another definition for the Thoma number is based on the downstream pressure p2:

(6.15.17)\[\sigma_{2} = \frac{p_{2} - p_{v}}{\Delta p}\]

where \(\sigma_{} = 1 + \sigma_{2}\) and \(\sigma_{2} = \frac{1}{X_f} - 1\)

6.15.2. Valve properties

6.15.2.1. Hydraulic specifications

Description

input

SI-units

Remarks

Characteristic type

Standard

Kv

Cv

Xi

Standard type

Buttrfly

Ball

Gate

Gate_sqr

if char.type = Standard, default = Buttrfly

Kv characteristic

table

[m3/h/√bar]

if char.type = Kv

Cv characteristic

table

[USGM/√psi]

if char.type = Cv

Xi characteristic

table

[-]

if char.type = Xi

Inner diameter

real

[m]

Initial setting

Position

P_upstream

P_downstr

Mass flow T_downstream

Initial position (open)

real

[-]

0 = closed
1= open

If init_set = Position

Initial upstream pressure

real

[N/m²]

If init_set = P_upstream

Initial downstream pressure

real

[N/m²]

If init_set = P_downstr

Initial mass flow

real

[kg/s]

If init_set = Mass flow

Check cavitation

Yes/No

Cavitation table

table

If check cavitation=Yes

Fraction gen. heat to fluid

real

[-]

Default = 1 (100%)

Deltares standard characteristics

Butterfly valve

\(\theta\)

\(\xi\)

0.000

1.0E+10

0.010

10000000

0.025

1700000

0.050

140000

0.075

23000

0.100

6000

0.125

2400

0.150

1150

0.200

440

0.250

195

0.300

97.5

0.400

31.0

0.500

13.8

0.600

5.80

0.700

2.40

0.800

1.00

0.900

.420

1.000

0.150

Ball valve

\(\theta\)

\(\xi\)

0.000

1.0E+10

0.015

900000

0.025

350000

0.050

40000

0.075

9500

0.100

2750

0.150

650

0.200

270

0.300

79.5

0.400

30.0

0.500

13.8

0.600

6.1

0.700

2.7

0.800

1.03

0.900

0.14

1.000

0.01

Gate valve

\(\theta\)

\(\xi\)

0.000

1.0E+10

0.0025

270000

0.025

2850

0.050

625

0.075

270

0.100

140

0.150

58

0.200

31

0.300

11.5

0.400

5.35

0.500

2.55

0.600

1.27

0.700

0.67

0.800

0.355

0.900

0.188

1.000

0.100

Square gate valve

\(\theta\)

\(\xi\)

0.000

1.0E+10

0.0025

249000

0.050

850

0.075

370

0.100

195

0.150

82

0.200

45

0.300

17.8

0.400

8.2

0.500

4.0

0.600

2.1

0.700

0.95

0.800

0.39

0.900

0.09

1.000

0.001

6.15.2.2. Component specific output

  • Valve position (open) [-]

  • Pressure ratio Xf system [-]

  • Generated Heat flux [W]

6.15.2.3. Actions

An activated valve can be opened or closed. How the valve opens or closes is arranged via a θ-time relation in tabular form.

An example:

Valve action table

Time (s)

Position (-)

0

0.5

10.0

12.0

14.0

0.5

18.0

0.5

Note: the position unit depends on the setting made in menu Units

The valve closes linearly in 0.5 s. It remains closed until 10 s. Then the valve opens again in 2 s and starts to close directly until theta = 0.5 at 14.0 s. From then on the valve remains in that position.

6.15.2.4. Component messages

Message

Type

Explanation

starts in open phase

Info

starts in closed phase

Info

Opens

Info

Closes

Info

Initial valve position below minimum position; minimum table value used

Warning

Initial valve position above maximum position; maximum table value used

Warning

Valve position truncated to input range

Warning

Indifferent valve position (zero discharge and zero dH) max. open position taken

Warning

Valve characteristic table entries not in between [0-1]

Error

The input table is not correct

Valve resistance in max. open position too large to obtain prescribed state

Error

The desired flow rate is too large for this valve with the calculated pressure drop.

Valve resistance in min. open position too small to obtain prescribed state

Error

Initial setting not physically realistic Discharge opposite to pressure drop

Error

Check your model or chose different settings.

Cavitation in steady state not allowed’

Error

Inconsistent valve position valve position between steady state results and action table; modify input

Error

The action table input for the valve position does not match with the Initial setting. The user should verify that the required Initial setting corresponds with the valve position of the action table. The values in the action table are allowed to deviate slightly from the Initial setting.